Features Of Surge Protector Circuit Breaker-SSD (Specific SPD Disconnector)
1. The SSD ( SPD Specific Disconnecotor) is special designed for SPD according to the requirements of IEC 61643-12: Low Voltage Surge Protective Device – Part 12: Surge Protective Device Connected to Low-voltage System – Selection and Application Principles (Edition 3.0 2020-05) , to solve the problem that when the SPD has power frequency leakage current or working freaueucy follow current due to deterioration or power frequency overvoltage, The SSD acts quickly to disconnect the SPD from the power frequency distribution system but does not act when the SPD discharges the lightning electromagnetic pulse current; it effectively solves the possibility of serious accidents such as burning and explosion in the application of the SPD, At the same time, it effectively solves the problem of protection dead zone when using a fuse or a circuit breaker as external disconnecting device. In low-voltage power distribution systems, it is an ideal companion device for voltage-switching SPDs and voltage-limiting SPDs.
2. With a special design, it can accurately distinguish and identify the power frequency current and the lightning electromagnetic pulse current, and automatically make the correct action.
3. It has the functions of large current flow, low residual voltage, small power frequency tripping current and short circuit protection tripping.
Note: It is forbidden to connect other loads at the end of the SSD(SCB).
Specification Of Surge Protector Circuit Breaker-SSD (Specific SPD Disconnector)
Models | TD-HA15 | TD-HA25 | TD-HA50 | TD-HB20 | TD-HB40 | TD-HB60 | TD -HB80 | TD-HB100 | TD-HB120 | TD-HB160 |
Test Standard | T1 T2 |
Normal Voltage | 230/400V AC |
Nominal discharge current(8/20μs)In | 50 | 60 | 80 | 10 | 20 | 30 | 40 | 50 | 60 | 80 |
Maximum discharge current(8/20μs)Imax | _ | _ | _ | 20kA | 40kA | 60kA | 80kA | 100kA | 120kA | 160kA |
Maximum discharge current(10/3500μs)Iimp | 15KA | 25KA | 50KA | _ | _ | _ | _ | _ |
| _ |
Frequency | 50/60Hz |
Rated short-circuit current capability Icn | 100kA | 100kA | 100kA | 15kA | 35kA | 50kA | 50kA | 100kA | 100kA | 100kA |
Matched SPD | Iimp 15kA | Iimp 25kA | Iimp 50kA | Imax 20kA | Imax 40kA | Imax 60kA | Imax 80kA | Imax 100kA | Imax 120kA | Imax 160kA |
Powerfrequency short circuit operating current Id | 3A |
Powerfrequency breaking times Tcn | 20ms |
Width of per pole | 36mm | 18mm | 36mm |
Powerfrequency breaking times | 10000 times |
IP Grade | IP20 |
Remote signal alarm | Option |
Cross section of connection wire | 2.5-35mm2 |
Working Temperature | —25℃~+60℃ |
Storge Temperature | —40℃~+75℃ |
Number of pole | 1P/2P/3P/4P |
Dimension of Surge Protector Circuit Breaker-SSD (Specific SPD Disconnector)
Diagram Of SCB SPD Circuit Breaker-SSD (Specific SPD Disconnector)