Feature of M100B AC Power Type 1 Surge Protector
Remote alarm.
large discharge current.
quick response.
Standardized module design, easy to install, simple for maintenance.
Latest arcing technology, avoid fire accident thoroughly.
Special impact fuse with high reliability.
The power supply protection devices own internationally famous core components with excellent performance.
Wiring Diagram of M100B Surge Protection Type 1
B1+N (L-N, N-PE) B3+N (L1/L2/L3-N, N-PE)
B2 (L/N-PE) B4 (L1/L2/L3-N, N-PE)
Application of M100B Type 1 Surge Protection Device
Type1 class I Whole House Surge Protective Device is an AC power surge protector for AC Power System.
Technical Parameters of M100B Type 1 Surge Protector
Model | M100B1 | M100B2 | M100B1+N | M100B4 | M100B3+N |
Lightning protection zone(LPZ) | 1-2 |
Standards Compliance | IEC61643-11, EN60950 |
Classification | Class I /Type 1 |
Nominal working voltage Un | 220V | 385V |
Max continuous operating voltage Uc | 385V |
Nominal discharge current (8/20µs) In | 50KA |
Max discharge current Imax (8/20µs) Imax | 100KA |
Follow current interrupt rating Ifi | 25KArms/100Arms |
Short-Circuit Current Rating Isccr | 25KA |
Temporary overvoltage (TOV)(L-N) Ut | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE) Ut | 1200 V / 200 ms – withstand |
Protection level @40kA, 8/20µs Up | 2100V |
Protection level @20kA, 8/20µs Up | 1500V |
Response time tA (L-N/N-PE) | 25ns/100ns |
Protection model | L-PE | L/N-PE | L-N, N-PE | L1/L2/L3, N-PE | L1/L2/L3-N, N-PE |
Dimension | 90 (H)×36(W)×65(L)mm | 90 (H)×72(W)×65(L)mm | 90 (H)×144(W)×65(L)mm |
Mounting | DIN-rail Mounting 35mm |
IP code | IP20 |
Working conditions | Temperature: -40 to 80℃, Relative humidity: ≤95% |
M100B AC Power Type 1 SPD Installation Diagram