2 in 1 monitor lightning arrester(power and video), a Kind of SPD, designed for analog video/ digital camera to protect camera power, video line from lightning electromagnetic pulse, induced over-voltage, operating overvoltage.
2 in 1 monitor lightning arrester(power and video), a Kind of SPD, designed for analog video/ digital camera to protect camera power, video line from lightning electromagnetic pulse, induced over-voltage, operating overvoltage.
Multi. Protection circuits, Gas-Tube+ TVS technology
Dual protection in Common module and different module
2 in 1 protection
TVS array technology, low capacitance
Multi-Strike Capability
Designed to protect monitor equipments (Power, Video), widely applied in bank monitor & safe guard system.
Monitor equipment for school, enterprise, road etc. security and protection.
Model | M10-12/D12BM | M10-24/D12BM | M10-220/D12BM |
Lightning projection zone(LPZ) | 2 | ||
Standards Compliance | IEC61643-1, EN60950,GB/T18802.21-2002,TB/T2311-2002, YD/T1235.2 | ||
According to IEC61643 | III | ||
According to DIN VDE6075 Part6(Draft 11.89) A1,A2 | D | ||
Max continuous operating voltage Uc | 12VDC | ||
Nominal discharge current (8/20µs) In | 3KA | ||
Max discharge current Imax (8/21µs) Imax | 5KA | ||
Transmission rate Vs | 100Mbps | ||
Limiting Voltage(10/700µs)component wire-Enclosure | 40V | ||
Nominal working voltage(Un) | 12V 24V 220V | ||
Max continuous operation voltage(Uc) | 15V 30V 275V | ||
Nominal discharge current Imax(8/20µs) | 5kA | ||
Max discharge current Imax(8/20µs) | 10kA | ||
Load current | 0.5A | ||
Protection level Up ( In) | 60V 100V 900V | ||
Response time (Ta) | 1ns | ||
Mounting | Be Installed between protected equipment and signal line | ||
Working conditions | Clamped type | ||
Dimension | 112*60*25mm | ||
Interface form | BNC | ||
IP code(IEC EN 60529) | IP20 | ||
Error rate | ≤10-12 | ||
Material/color | Aluminum/Blue | ||
Insertion loss | ≤.0.5dB | ||
Working conditions | Temperature: -40 to 85℃, Relative humidity: ≤95% |