DIN-rail mounted DC power Surge protective device(SPD)

DIN-rail mounted DC power Surge protective device(SPD)

DC power SPD, also called DC lightning arrestor or DC surge suppressor, is designed for the protection of DC power circuit from the damage of lightning overvoltage, induce over-voltage, transient operation, and resonance (Less than 100μs) overvoltage. Besides low voltage 12v, 24v DC surge protection devices, high voltage 600v, 1000v solar DC surge suppressors are also available. For the DC SPD price or other products of spd for power supply, such as ac spd, please feel free to contact us.


Feature of DIN-rail mounted DC power Surge protective device(SPD)

  • MOV structure

  • DIN-rail mounting for easy installation

  • Plug connectors for quick and easy connection or rewiring

  • Thermal disconnect device

  • Low residual voltage, fast response

  • Remote alarm 

  • Status indicator

  • CE certificated

Application of DIN-rail mounted DC power Surge protective device(SPD)

  • Widely used in communication equipment, DC power supply system. 

  • DC power systemDC switchboard, DC distribution board

  • DC distribution panels,DC power panels, DC power plant

  • Electronic information system power plant control

  • Switching mode power supply(SMPS Box, SMPS cabinet), high-frequency switching mode power supply,UPS system

  • BBU(Battery Backup Unit)RRU( remote radio unit)(RRH remote radio head) 

  • Integrated power supply                              

  • Data center, IDC power system, Column head cabinet

Technical parameters of DIN-rail mounted DC power Surge protective device(SPD)


ModelM10-24M15-48M20-24M20-48M40-24M40-48M40-220
Lighning proection zone(LPZ)1-2
Standards Compliance IEC61643-11,  EN60950
ClassificationClass II . C/D
Nominal working voltage Un24V48V24V48V24V48V220V
Max continuous operating voltage Uc30V75V30V85V30V85V320V
Nominal discharge current  (8/20µs)   In5KA10KA10KA10KA20KA20KA20KA
Max discharge current Imax (8/20µs)   Imax10KA15KA20KA20KA40KA40KA40KA
Protection level    8/20µs  Up280V400v350V400V500V550V1300V
Response time tA (L-N/N-PE)25ns
Protection model+、--PE
Dimension90 (H)×36(W)×66(L)mm
Recommend connecting line diameter(+- line /PE Line)≥4/6mm2≥4/6mm2≥4/6mm2≥4/6mm2≥6/10mm2≥6/10mm2≥6/10mm2
Mounting35mm DIN-rail Mounting 
IP codeIP20
Working conditionsTemperature: -40 to 80℃, Relative humidity: ≤95%


DIN-rail mounted DC power Surge protective device(SPD) Wiring Diagram

Wiring_Diagram_01.jpg

Wiring_Diagram_02.jpg


DIN-rail mounted DC power Surge protective device(SPD) Wiring Dimension

Dimension.jpg


Related Products

Leave a Message
contact
Contact Us
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy
Reject Accept